Over the next several weeks, we are publishing a series of blog posts that dive into each chapter of our 11 Things You Should Know About Infrared Windows guide. This series unpacks the technical details, practical tips, and real-world considerations that every maintenance professional needs to know when specifying, installing, and using IR windows. If you want the full picture right away, you can download the complete eBook here.
What Is Emissivity in Electrical Thermography?
Emissivity is a surface’s ability to emit infrared energy. It is expressed as a value between 0 and 1. A theoretical black body has an emissivity of 1, while highly reflective materials typically have much lower values.
A thermal camera detects infrared radiation and uses that information to calculate an apparent surface temperature. Because surfaces with different emissivity values emit different amounts of infrared energy at the same temperature, the camera must account for the emissivity of the target.
Electrical equipment contains materials with widely varying emissivity. Painted enclosures, cable insulation, rubber, and oxidized metals tend to have relatively high emissivity. Polished aluminum, copper, and stainless steel can have low emissivity and may reflect more infrared energy than they emit. This makes surface condition just as important as the material itself.
Why Emissivity Matters
When using infrared windows for inspections, one term comes up again and again: emissivity. Emissivity is a measure of how effectively a surface emits infrared energy. This value directly affects the accuracy of temperature readings captured by an IR camera. If emissivity isn’t properly understood or accounted for, inspections may produce misleading results, potentially masking early warning signs of failure.
How Emissivity Influences Inspections
Infrared thermography depends on detecting and measuring radiant heat. Surfaces with high emissivity (close to 1.0) emit energy consistently, allowing cameras to capture accurate temperature readings. However, highly reflective or polished surfaces—such as metals often found in electrical components—can have low emissivity. These surfaces reflect surrounding heat sources, making them appear hotter or cooler than they truly are.
This distinction is crucial in electrical inspections. A component might look like it’s operating normally when, in reality, a hot spot is developing beneath the surface. Misinterpretation caused by ignoring emissivity can delay maintenance actions and increase the risk of costly downtime or catastrophic equipment failure.

Why Emissivity Is Critical for Electrical Inspections
Electrical thermography is used to identify abnormal heating associated with loose connections, excessive resistance, overloaded circuits, deteriorating components, phase imbalance, and other developing problems. If emissivity is not properly considered, the temperatures displayed by the camera may not represent the actual condition of the equipment.
An incorrect reading can make a dangerous connection appear cooler than it is, delaying corrective action. It can also create a false hotspot caused by reflected heat from nearby equipment, the thermographer, or another source. Either error can result in poor maintenance decisions.
Emissivity is particularly important when absolute temperatures, alarm thresholds, or temperature differences are used to determine fault severity. Reliable trending also depends on consistent emissivity settings. If settings or measurement targets change between inspections, the apparent temperature trend may reflect the inspection method rather than a change in equipment condition.
Emissivity vs Reflectivity: What’s the Difference?
Emissivity describes how efficiently a surface emits its own infrared energy. Reflectivity describes how much infrared energy from surrounding objects is reflected by that surface toward the thermal camera.
Many electrical components are opaque to the infrared wavelengths used by common thermal cameras. For these surfaces, lower emissivity generally means higher reflectivity. A polished metal connection may emit relatively little infrared energy of its own while reflecting significant amounts of energy from nearby equipment, lighting, the sky, or the thermographer.
This relationship explains why shiny electrical components are difficult to measure accurately. The thermal camera receives a combination of emitted and reflected radiation. Without accounting for both emissivity and reflected temperature, the camera may calculate a temperature that is too high or too low.
High-emissivity surfaces are generally less reflective and provide more reliable temperature measurements. This is why approved high-emissivity labels, coatings, or reference targets are often used on low-emissivity electrical components.
Managing Emissivity in Practice
Adjust Camera Settings
Modern infrared cameras allow users to input emissivity values for more accurate readings. Knowing the approximate emissivity of the material under inspection ensures that the camera’s calculations reflect reality instead of distorted data.
Use Reference Materials
When possible, applying a material with known emissivity (like electrical tape or paint dots) provides a more reliable surface for measurement. This creates a stable reference point, reducing the uncertainty caused by reflective or variable surfaces.
Leveraging IR Windows
High-quality infrared windows minimize external variables that could distort emissivity readings. Because IR windows provide a consistent, non-intrusive inspection path, they reduce the risks associated with inconsistent measurement angles, fluctuating environments, or accidental contact with live equipment.
Training and Awareness
Even the best tools and equipment won’t guarantee accurate results without knowledgeable users. Investing in basic emissivity training ensures that inspectors understand how to recognize reflective errors, apply corrections, and maximize the value of IR windows. Building this awareness across maintenance teams can transform thermography from a routine task into a powerful predictive maintenance tool.

Common Emissivity Mistakes in Electrical Thermography
Several common mistakes can reduce the accuracy and repeatability of electrical inspections:
- Leaving the camera at 0.95 for every target: This setting may be suitable for some painted, insulated, or high-emissivity surfaces, but it is not appropriate for every electrical component.
- Relying only on an emissivity table: Published values are useful references, but the actual value can change with oxidation, corrosion, contamination, surface finish, temperature, and wavelength.
- Assuming color determines emissivity: A surface that looks dark in visible light does not necessarily have high emissivity in the infrared spectrum.
- Measuring polished metal without a reference target: Bright copper, aluminum, and stainless steel can produce unreliable temperature readings because of their low emissivity and high reflectivity.
- Ignoring reflected energy: A hot object, the thermographer, or even a cold sky can be reflected by the target and change its apparent temperature.
- Comparing different materials directly: A metal terminal, insulated cable, and painted enclosure may show different apparent temperatures even when their actual temperatures are similar.
- Using the wrong measurement angle: Highly reflective surfaces become more difficult to measure at extreme angles.
- Measuring a target that is too small: If the camera’s measurement area includes cooler or hotter background material, the displayed temperature will be an average of multiple surfaces.
- Ignoring equipment load: Electrical temperatures must be evaluated alongside operating load. A component inspected at light load cannot be compared directly with a previous reading taken under full load.
- Ignoring infrared window transmission: An IR window does not have an emissivity setting. It introduces transmission, reflection, and possible emission effects that must be accounted for separately.
- Applying tape or paint unsafely: Reference materials should only be installed when equipment is in a safe condition and the material is suitable for the voltage, temperature, and operating environment.
Best Practices for Accurate Emissivity Measurements
Accurate thermography requires a consistent inspection process rather than reliance on a single camera setting. Begin by identifying the target material and examining its surface condition. Polished, oxidized, painted, corroded, and contaminated versions of the same metal may have significantly different emissivity values.
Use the following practices to improve accuracy:
- Use an emissivity value appropriate to the material and its actual surface condition.
- Treat published emissivity tables as guidance rather than universal values.
- Use approved high-emissivity paint, tape, labels, or other reference targets where practical.
- Install reference materials while equipment is de-energized and follow all applicable safety procedures.
- Allow the reference material to reach the same temperature as the underlying component before taking a measurement.
- Account for reflected apparent temperature when quantitative accuracy is required.
- Change the camera angle to determine whether a suspected hotspot moves or disappears. A moving hotspot may be a reflection.
- Confirm that the target fills the camera’s measurement area.
- Maintain proper focus, distance, and viewing angle.
- Record equipment load, ambient conditions, emissivity, reflected temperature, distance, and camera settings.
- Use the same measurement points during repeat inspections.
- Compare similar components operating under similar loads.
- Verify the transmission characteristics of any infrared window in the optical path.
- Keep IR window optics clean and inspect them for damage or contamination.
- Use trained and qualified thermographers to capture and interpret the data.
For condition-based maintenance programs, repeatability is often as important as absolute accuracy. Consistent targets, inspection routes, loads, camera settings, and viewing positions make temperature trends more meaningful.
The Broader Impact of Emissivity
Understanding emissivity is a foundation for trust in thermal inspection results. Operations that train their teams to account for emissivity generate more reliable data, which leads to better condition-based maintenance strategies. In industries where uptime and safety are paramount, accuracy in thermography translates directly into reduced risk, optimized performance, and long-term savings.
The Takeaway
- Emissivity is the ability of a surface to emit IR energy and directly impacts inspection accuracy.
- Metals and reflective surfaces present challenges, but adjustments and reference points can help.
- IR windows support safer, more consistent thermography by limiting variables during inspections.
- Prioritizing emissivity awareness enhances reliability, safety, and cost savings in maintenance programs.
Dive Deeper Into IR Windows
There’s more to know, plus all the technical info you need to make informed decisions about safer inspections. Read our free Ebook: 11 Things You Should Know About Infrared Windows
FAQs About Emissivity in Electrical Thermography
What is emissivity in electrical thermography?
Emissivity is a measurement of how effectively an electrical component’s surface emits infrared energy. It is expressed as a value between 0 and 1 and is used by a thermal camera when calculating surface temperature. High-emissivity surfaces generally provide more reliable infrared measurements than polished, reflective metals.
Why is emissivity important for electrical thermography?
Emissivity affects how much infrared energy reaches the thermal camera from the target itself. If the camera uses an incorrect emissivity value, the displayed temperature may not represent the component’s actual temperature. This can hide developing faults, exaggerate minor temperature differences, or create false indications caused by reflected radiation.
How does emissivity affect thermal imaging accuracy?
A thermal camera calculates temperature based partly on the emissivity value entered by the thermographer. If the target has lower emissivity than the camera setting assumes, reflected energy may have a greater influence on the reading. Depending on the surrounding temperature, the component may appear hotter or cooler than it actually is.
What emissivity setting should I use for electrical inspections?
There is no single emissivity setting suitable for every electrical inspection. The correct value depends on the material, surface condition, temperature, camera wavelength, and measurement method. A setting near 0.95 is commonly associated with some paints, electrical tapes, labels, insulation, and other high-emissivity surfaces, but it should not automatically be used for bare metals. Inspectors should verify the target and use an appropriate reference value or high-emissivity target.
What is the difference between emissivity and reflectivity?
Emissivity is the ability of a surface to emit infrared energy. Reflectivity is the ability of that surface to reflect infrared energy from its surroundings. Low-emissivity metals are often highly reflective, which means the camera may detect more reflected energy and less radiation emitted by the component itself.
How can incorrect emissivity settings affect temperature measurements?
Incorrect settings can produce temperatures that are either too high or too low. This may cause a genuine fault to be underestimated, a normal component to be misclassified as a hotspot, or an inaccurate temperature trend to be created. The error becomes more significant when inspecting low-emissivity surfaces or when the target and surrounding objects have substantially different temperatures.
How do you improve emissivity when inspecting shiny electrical components?
A common approach is to create a stable high-emissivity measurement target using approved thermal paint, electrical tape, or a purpose-designed infrared label. The material should be installed while the equipment is de-energized, be suitable for the operating environment, and be allowed to reach the temperature of the underlying component. The thermographer can then measure the reference target instead of relying on the reflective metal surface.
What materials have low emissivity in electrical systems?
Bare or polished metals commonly have low emissivity. Examples include copper busbars, aluminum conductors, stainless steel, plated terminals, and polished metal connectors. Oxidation, corrosion, coatings, contamination, and surface roughness can increase the emissivity of these materials, so the surface condition must always be considered.
Can infrared inspection windows improve emissivity measurements?
Infrared windows do not change the emissivity of the electrical component. They can improve inspection consistency by providing a repeatable viewing location, angle, and distance while the enclosure remains closed. However, the window’s infrared transmission must be known and accounted for. The thermographer must compensate for both the target’s emissivity and the transmission characteristics of the installed optic.
What are the best practices for accurate emissivity measurements in electrical thermography?
Use values appropriate to the material and surface condition, account for reflected temperature, establish high-emissivity reference targets where practical, and maintain consistent measurement angles and distances. Inspectors should also document equipment load, environmental conditions, camera settings, and infrared window transmission. Repeat inspections should use the same targets and procedures so that temperature trends reflect actual equipment changes.