What Is the Arc Flash Hierarchy of Controls?
The arc flash hierarchy of controls is a structured approach to reducing the risk of injury from electrical arc events. It prioritizes removing hazards and reducing exposure before relying on procedures or protective clothing.
The commonly used five-level hierarchy consists of elimination, substitution, engineering controls, administrative controls, and personal protective equipment. Controls higher in the hierarchy generally depend less on individual behavior to remain effective.
NFPA 70E uses a closely related hierarchy of risk control methods that includes awareness as a separate level, positioned between engineering controls and administrative controls. Its electrical safety hierarchy therefore contains six levels.
For electrical maintenance, the practical starting point is to ask whether the hazard can be removed from the task. Where exposure remains, organizations should apply suitable layers of protection.
The Hierarchy of Controls in Electrical Safety
When addressing arc flash hazards, the hierarchy of controls provides a clear framework: eliminate or substitute hazards first, then apply engineering and administrative controls, and use PPE as the last line of defense. This structured approach ensures safety programs focus on designing out hazards rather than placing the burden on technicians.
The Hierarchy of Controls
From most to least effective, the Hierarchy of Controls consists of:
- Elimination: Physically remove the hazard from the workplace.
- Substitution: Replace a hazardous material or process with a less hazardous one.
- Engineering Controls: Isolate people from a hazard or remove the hazard at its source
- Administrative Controls: Develop procedures or change work habits to reduce exposure. These controls rely on human behavior and policies to manage risk.
- Personal Protective Equipment (PPE): Provide protective gear to workers to minimize exposure to hazards.
For example, elimination might mean redesigning a system to remove energized exposure points, while substitution could involve using lower-voltage equipment or technologies that allow inspections without opening energized panels. Engineering controls add barriers such as insulation or guarded enclosures. Only after these measures are in place should procedures and PPE be considered.

Elimination
Elimination removes the hazard from the work being performed. For electrical work, the clearest example is establishing and maintaining an electrically safe work condition before beginning the task.
This involves more than switching equipment off. The applicable process includes identifying energy sources, isolating them, controlling stored energy, applying lockout/tagout, verifying the absence of voltage, and applying grounding where required.
Until that process is complete, personnel must use the protective measures appropriate to the potential exposure. Adjacent energized equipment can also remain hazardous even when the equipment being serviced has been isolated.
Task design can eliminate the need for particular hazardous activities. For example, an infrared window may remove the need to take off a panel cover for a thermal inspection. That eliminates the cover-removal step, but it does not eliminate the energized electrical hazard inside the enclosure.
Substitution
Substitution replaces a hazardous design, process, or task with an alternative that presents less risk.
In electrical systems, this might involve replacing an accessible high-energy control arrangement with an appropriately designed lower-energy alternative. The replacement must be assessed as a complete system because a lower voltage alone does not establish that an arc flash hazard is absent.
At the task level, substituting a closed-panel inspection method for an open-panel method can reduce interaction with energized components. Infrared windows can enable this change where they provide adequate inspection coverage.
The distinction matters: the inspection method has changed, while the window itself functions as an engineering feature. Classification should reflect what the control actually does rather than assigning a product to one level in every application.
Engineering Controls
Engineering controls use equipment design or physical measures to reduce the likelihood of an incident, limit its consequences, or separate people from the hazard.
Examples include:
- Remote switching and racking: Allowing personnel to operate equipment from an assessed location away from the immediate hazard.
- Faster fault interruption: Using appropriately selected protective devices and settings to reduce arc duration.
- Arc detection systems: Detecting an arcing condition and initiating a rapid protective response.
- Current-limiting devices: Reducing fault energy where the device operates within its current-limiting range.
- Arc-resistant equipment: Directing or containing arc effects within the limits of its tested configuration.
- Inspection windows and permanent sensors: Reducing the need to open enclosures for suitable condition assessments.
- Barriers and interlocks: Restricting access or preventing particular unsafe equipment interactions.
Each measure has limitations. A remote operator must be positioned appropriately, protective settings require engineering evaluation, and arc-resistant equipment must be installed and operated according to its design.
Infrared windows do not automatically make an enclosure arc-resistant. Their installation must be compatible with the equipment and the intended inspection task.
Administrative Controls
Administrative controls establish how people plan, authorize, perform, and review electrical work.
They include:
- Written electrical safety procedures.
- Task-specific risk assessments.
- Job planning and pre-job briefings.
- Qualification and competency requirements.
- Energized work authorization where applicable.
- Access restrictions and work-area management.
- Inspection and maintenance schedules.
- Contractor coordination.
- Reporting and investigation of defects and near misses.
These controls help personnel recognize hazards and follow consistent methods. Their effectiveness depends on procedures being accurate, understood, and followed.
NFPA 70E separately identifies awareness, which includes measures such as warning signs, labels, and alarms. Awareness communicates a hazard; administrative controls direct how work is managed around it.
Neither a warning label nor an approved procedure removes the electrical energy that could sustain an arc.
Personal Protective Equipment (PPE)
PPE reduces the potential severity of injury when exposure remains after other controls have been applied. It does not prevent an arc flash from occurring.
Depending on the assessment, protection may include arc-rated clothing, a suitable face shield and balaclava or hood, eye protection, hearing protection, head protection, gloves, and footwear. Shock protection must be assessed separately, including the need for voltage-rated insulating equipment.
Selection depends on the task and the applicable incident energy analysis or PPE category method. A category table can only be used when the equipment and operating parameters meet its stated conditions.
PPE must fit correctly, be maintained, and be worn as intended. Arc-rated clothing also does not guarantee protection against every consequence of an event, including blast pressure and flying equipment fragments.
Why the Arc Flash Hierarchy of Controls Matters
The hierarchy helps organizations address the conditions that create exposure before deciding how employees should dress for the task.
This approach can improve safety and maintenance together. Better equipment design, accessible inspection points, and planned isolation can reduce the number of difficult energized interactions required during routine work.
It also encourages organizations to distinguish between three different objectives:
- Reducing incident likelihood: Making an arc event less likely to occur.
- Reducing exposure: Keeping personnel away from the hazard.
- Reducing consequences: Limiting the energy released or the injury sustained.
A control may support one objective without addressing the others. For example, remote racking can reduce operator exposure while leaving the possibility of an internal equipment fault.
Understanding these differences produces a more credible safety strategy and prevents overreliance on any single measure.
Designing Out Hazards Through Substitution and Engineering
Arc flash risk is most effectively reduced when design choices remove the need for live-panel work. In practice, this means substituting traditional inspection methods with alternatives that provide access without exposure.
Infrared windows and ultrasound ports are examples of substitution-level controls. Instead of opening energized cabinets, engineers design panels with built-in inspection points. These access points substitute the high-risk activity of removing a panel cover with a lower-risk activity: closed-panel inspection. The approach aligns with the Hierarchy of Controls and supports NFPA 70E Article 110, which emphasizes risk reduction before PPE.
Engineering controls extend this principle further by integrating lockout/tagout designs, insulation, or fault current limiters directly into equipment. By making safety inherent to the design, exposure to arc flash energy is minimized rather than managed at the worker level.
Role of Condition-Based Maintenance
NFPA 70B reinforces this philosophy by requiring structured, documented programs for electrical equipment maintenance. Condition-based maintenance is at the heart of this approach: instead of waiting for failures or conducting intrusive inspections, engineers rely on technologies that track asset health under load.
Infrared thermography through inspection windows, airborne ultrasound through access ports, and continuous temperature indicators all support the inspection intervals outlined in Annex J of NFPA 70B. By embedding these technologies into equipment design, facilities not only comply with the standard but also create safer, more efficient maintenance workflows.
How to Apply the Arc Flash Hierarchy of Controls
1. Define the task
Identify what personnel need to accomplish, which equipment is involved, and what interactions the work requires. Include inspection, testing, switching, troubleshooting, and maintenance.
2. Assess the equipment and exposure
Review the system configuration, equipment condition, available fault information, protective-device performance, and relevant working distances.
3. Evaluate elimination first
Determine whether an electrically safe work condition can be established for the task. Plan isolation and the work needed to achieve it.
4. Consider a safer alternative
Ask whether the task or design can change. Inspection access, external interfaces, or a different control arrangement may reduce hazardous interaction.
5. Evaluate engineering improvements
Have qualified personnel assess appropriate measures such as remote operation, faster fault clearing, barriers, or permanent inspection access.
6. Apply awareness and administrative measures
Provide appropriate labels, warnings, work instructions, training, authorization, and access control. Account for foreseeable human error.
7. Select protection for the remaining exposure
Determine the required PPE from the assessment and applicable selection method. Purchasing more protective clothing does not, by itself, justify energized work.
8. Verify and review
Confirm that controls work as intended. Reassess when equipment, protection settings, operating conditions, or work methods change.
Compliance and Liability Considerations
The regulatory landscape underscores why designing out hazards matters. NFPA 70E requires risk assessments for energized work and reduces PPE categories when closed-panel inspections are possible (Table 130.5(G)). NFPA 70B mandates documented programs that prioritize non-intrusive, repeatable inspection methods. OSHA regulations further emphasize the need to eliminate or substitute hazards wherever possible under the Hierarchy of Controls.
For engineers, this means safety is no longer optional or reactive. Designing equipment with built-in inspection access and maintenance capabilities ensures compliance is achieved by design, and long before a technician puts on PPE.
Mini Case Study: Substitution-Level Controls in a UK Automotive Plant
A leading UK automotive manufacturer experienced an arc flash event that displaced a transformer’s cable connection door. The incident highlighted critical vulnerabilities in their electrical systems. With downtime posing a significant risk to production and safety, they adopted a two-stage strategy leveraging thermal inspections and ultrasound partial discharge monitoring. By installing infrared inspection windows and ultrasound ports, the team was able to conduct safer, non-intrusive condition-based maintenance, eliminating the need to open energized panels. This substitute-level control, embedded into system design, aligned with the hierarchy of controls and supported NFPA 70B’s emphasis on structured, automated inspection workflows.
The system upgrades were implemented during a scheduled shutdown, minimizing operational impact while enhancing safety and inspection efficiency. Since deployment, the facility has transitioned from reactive to proactive maintenance, consistently monitoring critical electrical components without exposing personnel to arc flash hazards. This case reflects how engineering-forward solutions, written into equipment design rather than enforced via PPE or procedures, advance compliance and reliability in line with NFPA standards.
Practical Design Strategies for Engineers
Practical steps to design out arc flash hazards include:
- Incorporating inspection access such as IR windows and ultrasound ports at the specification stage.
- Standardizing enclosures with built-in safety features like interlocks and insulated barriers.
- Deploying continuous monitoring technologies for high-energy equipment, reducing the need for live inspections.
- Documenting equipment designs in a way that supports condition-based maintenance intervals and audit readiness.
By addressing safety in the design phase, engineers reduce long-term operational risk and make compliance easier to sustain.
Key Takeaways
- Applying the hierarchy of controls ensures arc flash risk is addressed through design, not left to administrative procedures or PPE alone.
- Substitution and engineering controls, such as inspection windows and ultrasound ports, support NFPA 70E and NFPA 70B requirements for safer, condition-based maintenance.
- Embedding hazard-reduction features into equipment design reduces liability, improves compliance, and creates safer, more efficient maintenance practices.
Arc Flash Hierarchy of Controls Examples
- Repairing an electrical connection
A facility schedules an outage and establishes an electrically safe work condition before repair. This applies elimination to the work area, while appropriate controls remain necessary during isolation and verification.
- Redesigning a control circuit
An equipment designer replaces an accessible higher-energy control arrangement with a suitably engineered lower-energy system. This applies substitution after confirming that the replacement reduces the relevant hazards.
- Inspecting enclosed electrical equipment
A maintenance team uses infrared windows to collect suitable thermal images without removing the main panel covers. The window provides engineering access and supports substitution of the inspection method. The internal equipment remains energized.
- Racking a circuit breaker
A remote racking arrangement allows operation from a location selected through the risk assessment. This is an engineering control that separates the operator from the immediate equipment hazard.
- Managing necessary energized testing
The organization assesses and authorizes the task, uses qualified personnel, controls access, and applies suitable tools and PPE. Administrative measures and PPE address the exposure that remains after higher-level options have been considered.
Arc Flash Hierarchy of Controls Comparison Table
| Control level | Main purpose | Electrical example | Important limitation |
|---|---|---|---|
| Elimination | Remove the hazard from the task | Establish an electrically safe work condition before repair | Isolation and verification can involve exposure before completion |
| Substitution | Replace a hazardous arrangement with a less hazardous alternative | Redesign an accessible circuit to reduce available energy | The replacement requires assessment for remaining or new hazards |
| Engineering controls | Change equipment or physically separate personnel from hazards | Remote racking, rapid fault interruption, inspection windows | Effectiveness depends on design, installation, operation, and maintenance |
| Administrative controls | Establish safe work methods and responsibilities | Task planning, qualification, authorization, and access control | Depends on people understanding and following the process |
| PPE | Reduce injury severity from remaining exposure | Appropriate arc-rated clothing and protective equipment | Does not prevent the event or protect against every consequence |
NFPA 70E also places awareness between engineering and administrative controls. Examples include warning labels, signs, and alarms.
Safer by Design
Arc flash hazards can’t be eliminated with PPE alone—they must be designed out. By incorporating infrared inspection windows and ultrasound ports, organizations replace high-risk live-panel work with safer, closed-panel inspections. These substitution-level controls align directly with NFPA 70E’s hierarchy of risk reduction while enabling consistent, condition-based maintenance under NFPA 70B.
Contact IRISS today to learn how a substitution-approach to inspection access and condition-based maintenance tools can help your team reduce arc flash exposure, protect workers, and sustain compliance.
FAQs
These questions address how the hierarchy applies to electrical tasks, equipment design, and worker protection.
What is the Arc Flash Hierarchy of Controls?
It is a prioritized method for reducing arc flash risk. Organizations first consider removing the hazard, then progressively evaluate safer alternatives, engineering measures, work controls, and PPE.
The purpose is to reduce dependence on protective clothing and individual behavior by addressing hazards earlier in the work-planning and equipment-design process.
What are the five levels of the Arc Flash Hierarchy of Controls?
The five levels in the general hierarchy are elimination, substitution, engineering controls, administrative controls, and PPE.
NFPA 70E adds awareness as a separate level between engineering and administrative controls. Its hierarchy therefore contains six risk control methods.
Why is elimination the most effective control for arc flash hazards?
Elimination removes the hazardous energy from the task rather than relying on measures that manage exposure to it.
Once an electrically safe work condition has been properly established and maintained, the isolated parts cannot sustain an electrically supplied arc flash. Other energy sources and adjacent energized equipment must still be addressed.
How do engineering controls reduce arc flash hazards?
Engineering controls can reduce the likelihood of an event, shorten its duration, limit released energy, or separate personnel from the equipment.
Examples include protective-device improvements, arc detection, remote operation, barriers, and suitable inspection access. Their effectiveness depends on the particular system and how the equipment is maintained and operated.
How can arc flash hazards be reduced?
Start by eliminating energized exposure where required and feasible. Then evaluate safer designs and tasks, engineering improvements, equipment maintenance, warning systems, work procedures, and appropriate PPE.
Condition monitoring can help identify some developing defects, but it cannot detect every possible cause of an arc flash. Findings must lead to timely investigation and corrective action.
What does NFPA 70E say about the Arc Flash Hierarchy of Controls?
NFPA 70E incorporates the hierarchy into its risk assessment approach. Its order is elimination, substitution, engineering controls, awareness, administrative controls, and PPE.
The practical requirement is to evaluate risk reduction in that order, giving priority to eliminating the hazard. Choosing PPE is one part of the process, not a replacement for assessing the task and considering higher-level controls.
What PPE is required for arc flash protection?
The required PPE depends on the task, equipment, and assessed exposure. Selection uses an incident energy analysis or the applicable PPE category method within its limitations.
The ensemble may include arc-rated clothing, face and head protection, safety glasses, hearing protection, gloves, and suitable footwear. Shock protection requirements must also be evaluated. There is no single PPE set appropriate for every electrical task.
What is the main cause of an arc flash?
An arc flash occurs when electrical current travels through an unintended arcing path. There is no single initiating cause for every event.
Possible contributors include insulation deterioration, contamination, moisture, damaged equipment, loose connections, foreign objects, and errors during equipment interaction. The available electrical energy and protective-device response strongly influence the resulting severity.
What is the safe distance for arc flash?
There is no universal safe distance. The arc flash boundary is determined for the equipment and relevant conditions, using an analysis or an applicable table method.
It represents a thermal exposure boundary, commonly associated with incident energy of 1.2 cal/cm². It is separate from shock approach boundaries and does not guarantee protection from every blast or projectile hazard. Personnel must follow the distances and controls established for the task.
Why are engineering controls preferred over PPE for arc flash safety?
Engineering controls can reduce exposure or fault energy before an event reaches the worker. They generally rely less on repeated individual decisions than protective clothing does.
PPE remains important where exposure persists, but it acts at the point of exposure. A stronger safety approach reduces the hazard and the need for hazardous interaction while maintaining the protection required for the remaining risk.